11258421.10 08/2014 GB/D

WIKA operating instructions model T32.xS

37

The version T32.1S.0lS is designed for installation in housings or

connection heads in areas with 1G, 2G or 1D, 2D requirements.

The version T32.3S.0IS is intended for installation in a housing

which guarantees at least protection class IP 20 (2G application or

installation outside the hazardous area) or IP 6x (2D application).

10.2 Specific conditions for safe use
T32.3S.xxx:

The surface of the case is not conductive. The temperature transmitter

must be mounted in a way that electrostatic charges will not occur.

T32.xS.0NI (use as non-incentive equipment II 3G Ex nA):

Disconnection of power supply is forbidden inside the hazardous

area. When connecting or disconnecting the terminals ensure the

power supply is disconnected outside the hazardous area.

These temperature transmitters must be mounted in a case that

must at least correspond to following ingress protection IP 54 in

accordance with EN 60529/IEC 60529.

The holes in the connection terminals (T32.1S.0NI) or the additional

connections labelled “Modem” (T32.3S.0NI) shall not be used in

connection with type of protection nA.

When during use in circuits with the safety class nA (non-incendive)

the permissible connected loads have been exceeded for a short

term

1)

, the use of these transmitters in circuits with the safety class

Ex nL (energy limited) is not permissible any more.

1) When the transmitters are used in circuits with the safety class nA, it is permissible to exceed the

maximum supply voltage by up to 40 % for a short term.