WIKA T32.xS Benutzerhandbuch

Seite 38

Advertising
background image

GB

11258421.10 08/2014 GB/D

38

WIKA operating instructions model T32.xS

T32.xS.0IS, T32.xS.0IS-x (providing IS level of protection Ex ia *)
Installation in the save area:

The transmitter shall be mounted inside a housing providing as a

minimum degree of protection IP 20 according to IEC 60529.

Wiring inside the housing shall comply with clause 6.3.12 and

clause 7.6.e of IEC 60079-11:2011.

Terminals or connectors for the intrinsically safe circuits shall be

arranged according to clause 6.2.1 or 6.2.2 of IEC 60079-11:2011

respectively.

Installation in EPL Ga (Zone 0) or EPL Gb (Zone 1) area

Transmitter models T32.1S.0IS, T32.1S.0IS-x:

- Due to application, the transmitter shall be mounted inside a

housing, suitable for installation in EPL Ga (Zone 0) areas and

wherein electrostatic charge effects are excluded.

- Due to application, the transmitter shall be mounted inside a

housing, suitable for installation in EPL Gb (Zone 1) areas.

Transmitter models T32.3S.0IS, T32.3S.0IS-x:

The transmitter shall be mounted inside a housing, suitable for

installation in EPL Gb (Zone 1) area and wherein electrostatic

charge effects are excluded.

Installation in EPL Da (Zone 20) or EPL Db (Zone 21) area

Transmitter models T32.1S.0IS, T32.1S.0IS-x:

Due to application, the transmitter shall be mounted inside a

housing, suitable for installation in EPL Da (Zone 20) or EPL Db

(Zone 21) area, providing degree of protection IP 6x according to

IEC 60529.

Transmitter models T32.3S.0IS, T32.3S.0IS-x:

Due to application, the transmitter shall be mounted inside a

housing, suitable for installation in EPL Db (Zone 21), providing

degree of protection IP 6x according to IEC 60529.

10. Notes for mounting, operating in ...