WIKA T32.xS Benutzerhandbuch

Seite 38

Advertising
background image

GB

11258421.10 08/2014 GB/D

38

WIKA operating instructions model T32.xS

T32.xS.0IS, T32.xS.0IS-x (providing IS level of protection Ex ia *)
Installation in the save area:

■

The transmitter shall be mounted inside a housing providing as a

minimum degree of protection IP 20 according to IEC 60529.

■

Wiring inside the housing shall comply with clause 6.3.12 and

clause 7.6.e of IEC 60079-11:2011.

■

Terminals or connectors for the intrinsically safe circuits shall be

arranged according to clause 6.2.1 or 6.2.2 of IEC 60079-11:2011

respectively.

Installation in EPL Ga (Zone 0) or EPL Gb (Zone 1) area

■

Transmitter models T32.1S.0IS, T32.1S.0IS-x:

- Due to application, the transmitter shall be mounted inside a

housing, suitable for installation in EPL Ga (Zone 0) areas and

wherein electrostatic charge effects are excluded.

- Due to application, the transmitter shall be mounted inside a

housing, suitable for installation in EPL Gb (Zone 1) areas.

■

Transmitter models T32.3S.0IS, T32.3S.0IS-x:

The transmitter shall be mounted inside a housing, suitable for

installation in EPL Gb (Zone 1) area and wherein electrostatic

charge effects are excluded.

Installation in EPL Da (Zone 20) or EPL Db (Zone 21) area

■

Transmitter models T32.1S.0IS, T32.1S.0IS-x:

Due to application, the transmitter shall be mounted inside a

housing, suitable for installation in EPL Da (Zone 20) or EPL Db

(Zone 21) area, providing degree of protection IP 6x according to

IEC 60529.

■

Transmitter models T32.3S.0IS, T32.3S.0IS-x:

Due to application, the transmitter shall be mounted inside a

housing, suitable for installation in EPL Db (Zone 21), providing

degree of protection IP 6x according to IEC 60529.

10. Notes for mounting, operating in ...