WIKA operating instructions model T32.xS

Maximum permissible load depending on the supply voltage:

Load diagram

11289130.02

Voltage U

B

in V

Load R

A

in Ω

Ex ia Ex nA/ic

For the power supply, use an energy-limited electrical circuit (EN/UL/

IEC 61010-1, section 8.3) with the following maximum values for the

power supply:

for U

B

= DC 42 V; 5 A

For the external power supply a separate switch is required.

9.2 HART

®

loop display (DIH50, DIH52)

Additional configuration of the temperature transmitter with a HART

®

Loop Display is possible. This is used for the local display of the

current process value. The unit and the configured measuring range

of the transmitter are automatically updated via the HART

®

protocol

in the display. No further change of the HART

®

loop display is

necessary. To do this, the display must be in HART

®

mode.