Commissioning, operation – WIKA T32.xS Benutzerhandbuch

Seite 24

Advertising
background image

GB

11258421.10 08/2014 GB/D

24

WIKA operating instructions model T32.xS

Further information on the configuration of the T32 with

the software tools mentioned above is available on

request.

6.3.2 DD version

The model T32.xS temperature transmitter can be used with the

following DTM and DD versions.

T32 HART

®

instrument revision

Corresponding

DD

(Device Description)

T32 HART

®

DTM

0

Dev v0, DD v2

DTM 1.0.2

1

Dev v1, DD v1

DTM 1.0.2

2

Dev v2, DD v1

DTM 1.0.2

3

Dev v3, DD v1

DTM 2.0.0.175

6.3.3 HART

®

communicator (HC275, FC375, FC475, MFC4150)

With the HART

®

communicator the instrument functions are selected

via various menu levels and with the help of a special HART

®

function

matrix (see chapter 6.5 “HART

®

configuration tree”).

6.4 Connection of FSK modem, HART

®

communicator

WARNING!

The measuring circuit has to have a load of at least

250 Ω.

For all transmitters with hazardous area protection

observe chapter 10 “Notes for mounting and operating

in hazardous areas”.

This resistor is already integrated in most power supplies available

in the market and is therefore not required separately. Frequently a

special connection for the FSK modem is already available.

6. Commissioning, operation