Explanation of symbols

Before mounting and commissioning the instrument, ensure you read the

operating instructions!

CE, Communauté Européenne

Instruments bearing this mark comply with the relevant European directives.

ATEX European Explosion Protection Directive

(Atmosphère = AT, explosible = EX)

Instruments bearing this mark comply with the requirements of the European

Directive 94/9/EC (ATEX) on explosion protection.

3. Specifications

3.1 Resistance thermometer
Sensor connection method

2-wire

3-wire

4-wire

Limiting error of the sensor per DIN EN 60751

Class B

Class A

Class AA

The combination of a 2-wire connection with class A or class AA is not permissible, since the

lead resistance of the measuring insert negates the higher sensor accuracy.

Basic values and limiting errors

Basic values and limiting errors for the platinum measurement resistances are laid down in

DIN EN 60751.

The nominal value of Pt100 sensors is 100 Ω at 0 °C.

The temperature coefficient α can be stated simply to be between 0 °C and 100 °C with:

α = 3.85 ∙ 10

-3

°C

-1

The relationship between temperature and electrical resistance is described by polynomialss,

which are also defined in DIN EN 60751. Moreover, this standard specifies the basic values in °C

steps in tabular form.