Electrical connection values – WIKA TR10-A Benutzerhandbuch

Seite 30

Advertising
background image

3345267.12 01/2014 GB/D

30

WIKA operating instructions RTD and TC, intrinsically safe designs (Ex i)

GB

7.4.3 Partition wall for use in Zone 0 or Zone 1/2 or separation between hazardous area

and non-hazardous area

If the wall thickness is less than 1 mm, the instrument must also be marked with an “X” or a safety

instruction in accordance with 29.2 of EN/IEC 60079-0, with the special proviso that for safe use

it must not be subjected to ambient stresses that may have an adverse effect on the partition

wall. If the partition wall is continuously subjected to vibrations (e.g. vibrating membranes), its

fatigue limit at the maximum amplitude must be stated in the documentation (see Section 4.2.5.2,

EN/IEC 60079-26).

Alternatively, a thermowell of suitable minimum wall thickness may be used by the customer.

When using a thermowell/neck tube, the overall instrument must be constructed such that

it allows installation in a way that results in a sufficiently tight gap (IP 67) or a flame path

(EN/IEC 60079-1) towards the less hazardous area.

8. Electrical connection values

8.1 Electrical data without built-in transmitter or digital display

For Group II instruments (potentially explosive gas atmospheres)

3)

, t

he following maximum

connection values apply:
U

i

= DC 30 V

I

i

= 550 mA

P

i

(at the sensor

1)

) = 1.5 W

For Group II instruments (potentially explosive dust atmospheres), the following maximum

connection values apply:
U

i

= DC 30 V

I

i

= 550 mA

P

i

(at the sensor

2)

) = For the values, see “Table 2” (column 2), chapter 7.1.2 “Ex marking”

1) The permissible power to the sensor depends on the temperature of the medium T

M

, the temperature class

and the thermal resistance R

th

, but shall not be more than 1.5 W.

For calculation examples, see chapter 9 “Calculation examples for self-heating at the sensor/thermowell tip”.

2) The permissible power to the sensor depends on the temperature of the medium T

M

, the maximum allowed

surface temperature and the thermal resistance Rth, but shall not be more than the values from “Table 2”

(column 2), see chapter 7.1.2 “Ex marking”.

3) Use in methane atmospheres

Owing to the higher minimum ignition energy of methane, the instruments can also be used where methane

causes a potentially explosive atmosphere. The instrument can be optionally marked with IIC + CH

4

.

The internal inductance (L

i

) and capacitance (C

i

) of standard measuring inserts in accordance

with DIN 43735 are negligible. The values for cable probes and very long sheathed-cable/

resistance thermometers can be seen from the rating plate and must be taken into account when

connecting them to an intrinsically safe power supply.

7. Information on mounting and ... / 8. Electrical connection values

Advertising
Dieses Handbuch ist für die folgenden Produkte bezogen werden: