IMP Pumps ECL Benutzerhandbuch

Seite 23

Advertising
background image

-23-

GB

protections start operating. The converter is

in a blocked state. On the front side, a light

diode is switched on (ALARM, ERROR). The

control impulses in the transistor connections

(IGBT) are disabled in this position. Before

starting, it is necessary to unblock it by

pressing the RESET key (factory settings are

programmed for an automatic RESET).

START/STOP:

After giving the START command, the

electric motor starts on an expected course.

With the command STOP, the electric motor

stops in the expected time.

F) Setting the pump operational point:

Each heated device has its specific needs

for the quantity of flow and pressure drop of

the circulating heated medium defined by the

architect of the heating device. The heating

device will operate most efficiently, and most

energy will be saved if the pump gave the ex-

act pressure and quantity of heated medium

that the heated device needs. That is why it is

expedient to set the pump operational point

as precisely as possible to the heated device

requirements.

When using the meter P, we set the pressure

drop in the heated device with an appropriate

turn to the pressure difference adjustor placed

on the meter P to the value defined by the ar-

chitect of the device. The pump will keep the

set pressure difference value, independent of

the quantity of flowing medium, which is de-

fined by the position of individual valves of the

heated device. The set difference value can

be read indicator of the adjustor P.

G) Setting the frequency converter and

pump factory settings

Each ECL pump has factory settings to

achieve the technical properties indicated in

the catalogue.

By changing the factory settings of the inbuilt

frequency converter it is possible to achieve

some other special functions of the pump,

such as pump operation at a constant fre-

quency, or the possibility of external regula-

tion by switching to different pre-set frequen-

cies (up to 16 pre-set frequencies). It is also

possible to increase or decrease the pump

power within certain limits, while it is also pos-

sible to change the settings of the pump pro-

tection and similar.

Changes to the factory

settings of the frequency converter can

only be done by an authorised servicer

with a serving operator, which is necessary

for setting the inbuilt frequency converter.

Without a serving operator, it is not

possible to change the set values of the

inbuilt frequency converter.
H) Shutting down the pump

Before dismantling the pump, it is necessary

to mechanically disconnect the cables

from the connection cabinet and prevent a

possible electric start-up of the pump. We

close the valves on the suction side, control

the lock on the pressure side, and prepare

the pump for dismantling.

6. M

aintenance

and

disMantling

- Maintenance must be done regularly

according to the periodic plan of reviews.

The pump must operate calmly, without

tremors, and always filled with medium.

- Operating the pump at ambient tempera-

tures higher than 40°C is not recommend-

ed. The temperature of the bearing (the

external side of the bearing mounting) must

not exceed 90°C. The maximum tempera-

ture of the medium is given in the technical

details on the display plate of the pump.

- The flow of the medium through the pump

must be enabled, as longer operation

of the pump with closed valves on the

pressure side is not permitted.

- With damaged mechanical seals, care

should be taken that the medium does not

penetrate to the electric motor, as it can

cause permanent damage. It is necessary

to inspect the other seals (flat, O-ring), and

watch for the occurrences of leaks at the

contacts. When the seals are worn out, they

need to be replaced.

- If the pump remains idle for a longer

period, it is recommended to start-up the

pump for 5 minutes weekly according the

same instructions as for the initial start-up.

- The inspection of bearings should be more

frequent in adverse operating conditions.

The manufacturer foresees a minimum of

20000 hours of operation. Interventions

to the pump can only be done by a

professional or a maintenance service.