C5) CURRENT OVERLOAD (CONVERTER

THERMAL PROTECTION):

If the frequency converter is constantly

loaded with a current larger than the

one given, or with a current smaller than

the value accepted by the overloading

protection, then the temperature of the

converter cooling element increases and

the current overload protection or converter

thermal protection starts operating.

Possible causes are:

- Under-dimensioned drive. Removing error:

replace the frequency converter with a

stronger one. If the electric motor current

is larger than the one given, the whole

electric motor converter is replaced.

- Frequency of severe operating pace.

Removing error: programme the

intermittence pace and activate the RESET

key on the converter.

WARNING:

WARRANTY IS NOT

RECOGNISED!

- FOR UNJUSTIFIED INTERVENTIONS

IN PUMP WITH ANY MODIFICATIONS

WITHOUT THE PERMISSION OF AN

AUTHORISED SERVICER OR THE

MANUFACTURER

- FOR USE OF SPARE PARTS THAT ARE

NOT ORIGINAL OR AUTHORISED BY

THE MANUFACTURER

- FOR CHANGING THE FACTORY

SETTINGS OF THE FREQUENCY

CONVERtER IN tHE ABSENCE OF

AN AUTHORISED SERVICER OR

THE FREQUENCY CONVERTER

MANUFACTURER’S SERVING

OPERAtOR

- FOR IMPROPER STORAGE OF THE

UNCONNECTED PUMP

- FOR DISREGARDING THE TECHNICAL

INSTRUCTIONS