IMPAC pyrometers ISR 12-LO/GS

27

98 = global address without response (only setting commands!)

Baud rate:

AAbrX

X = 1 ... 6 or 8 (dec.)
1 = 2400 baud

4 = 19200 baud

(7 is not available)

2 = 4800 baud

5 = 38400 baud

8 = 115200 baud

3 = 9600 baud

6 = 57600 baud

Temp. display °C / °F

AAfhX

Output: X = 0: display in °C; X = 1: display in °F

Reading signal strength AAtr

Output: XXXX, 1000 equivalent to 100.0%

Wait time:

AAtwXX

XX = 00 ... 99 (decimal)

Warning level
dirty window

AAdwXX

XX = 00 … 99; 2 digit, dec. in %

Error status:

AAfs

Output: XX;

XX=00…FF (00 = no error)

(01…FF: error code for LumaSense service)

Internal temperature:

AAgt

Output: XXX (dec. 000 ... 099, at °C, 032 ... 210 at °F)

Max. internal temp.:

AAtm

Output: XXX (dec. 000 ... 099, at °C, 032 ... 210 at °F)

Reading interface type:

AAin

Output: X = 1 or 2; 1 = RS232, 2 = RS485

Laser targeting light:

AAlaX

X = 0 switch off laser targeting light
X = 1 switch on laser targeting light

Lock keyboard:

AAlkX

X = 0 ... 3
1 = lock lk1, removal with command lk0 or power off-on
0 = removal of lock lk1
3 = continuous lock lk3, removal only with command lk2
2 = removal of lock lk3

Reading parameters:

AApa

Output decimal 11-digit:

Digit 1 und 2 (10...99 or 00):

ε

Digit 3 (0 ... 6): t

90

(exposition time)

Digit 4 (0 ... 8): t

CL

(max. storage clear mode)

Digit 5 (0 ... 1): analog output

Digit 6 und 7: (00 ... 98): temperature

Digit 8 und 9 (00 ... 97): address

Digit 10 (0 ... 6 or 8): baud rate

Digit 11 (0): (0 or 1): keyboard active or locked

Digit 12 ... 15 (0800 ... 1200): emissivity slope

Autoreset:

AAre

Activating auto-reset, initializes the pyrometer new and

resets the instrument to default settings

Reference number:

AAbn

Output: XXXXXX (hex 6-digit)

Serial number:

AAsn

Output: XXXX (hex 4-digit)

Device type /
software version:

AAve

Output: XXYYZZ (6-digit decimal)

XX = 06 (ISR 12-LO)
YY = month of software version
ZZ = year of software version

Software version
in detail:

AAvs

tt.mm.yy XX.YY
tt = day; mm = month; yy = year; XX.YY = software version

Device type:

AAna

Output: “ISR 12-LO“ (16 ASCII-characters)

Special pouring stream commands
Description

Command

Parameters

Reading of data

AAtg

Output: ABBBCCCC
A = serial no. of pouring date, Ascii-Hex 0 … F
BBB = time of pouring Ascii-Hex 000 … FFF in

1

/

10

s

(pre-run time + measuring time)

CCCC = temp. value Ascii-Hex 0000 … FFFF in

1

/

10

°C or °F

Pouring stream mode

AAtoXX

Output: XX XX = 00 pouring stream mode off

XX = 01 pouring stream mode on

Measuring condition

AAtqXX

XX = 00 … 99; 2 digit, dec. in % of 1024 meas. values

Pre-run time

AAtpXX

XX = 00 … 99; 2 digit, dec. in

1

/

10

s

Measuring time

AAmtXX

XX = 00 … 99; 2 digit, dec. in

1

/

10

s; 00=Automatic mode

Follow-up time

AAtnXX

XX = 00 … 99; 2 digit, dec. in

1

/

10

s

Note: the letter “l” means the lower case letter of “L”.