Burkert Type 4040 Benutzerhandbuch
Seite 10

8 - 4040
english
I/O Structure for Type 4040
OPERATIONAL INSTRUCTIONS
Abbrevia-
tion
Physical value
Scalable
value
Electri-
cal cur-
rent
Resolu-
tion
Port
1) Supply:
24 V DC
F3
2) Analog inputs:
Main pressure
p1
4-20 mA
0-10 bar
8 bits
B13
Conveying pressure
p
4-20 mA
0-10 bar
8 bits
B12
Actual temperature
T1
4-20 mA
0-160 °C
8 bits
B11
3) Analog outputs:
Target value setting
Lift
4-20 mA
0-100 %
4-20 mA
8 bits
B5
Output conveying pres-
sure
p_out
4-20 mA
0-10 bar
4-20 mA
8 bits
B6
4) Digital inputs:
Lock_max_alarm
PIA 01
0/24 V
0/1
C6
Buffer_full
LIA
0/24 V
0/1
C7
Sealing_air_alarm
PIA 02
0/24 V
0/1
C8
Start/Stop
0/24 V
0/1
C10
Empty run
0/24 V
0/1
C11
Reset alarm
0/24 V
0/1
C12
Key-operated switch
0/24 V
0/1
C13
5) Digital outputs:
Sealing_air
XOV 01
0/24 V
0/1
0.5 A ind.
A2
Lock_in
Motor 01
0/24 V
0/1
0.5 A ind.
A3
Alarm - red
0/24 V
0/1
A4
Standby - green
0/24 V
0/1
A5
Conveying - white
0/24 V
0/1
A7
6) Serial connection
RS232 (for diagnostics)
H
O
PERATION