11 inputs / outputs – Baumer BA ZADM023 Benutzerhandbuch

Seite 69

Advertising
background image

Seite / Page 69

11

Inputs / outputs

11.1 Analog output

The zero point of the measuring range is on the left side (written on sensor). Depending on position
of the object and the type of measurement, the current is between 4 – 20 mA.


11.2 Switching output

Depending on the threshold values and the measuring value, the switching output (or the two
switching output, depending on sensor type) is High or Low.

Logic of the switching output (one switching output)
If threshold 1 < threshold 2; the switching output is ON if the measured value is between threshold 1
and threshold 2, otherwise OFF
If threshold 1

>

threshold 2; the switching output is OFF if the measured value is between threshold 1

and threshold 2, otherwise ON

Logic of the switching output (two switching outputs)

If measured value > threshold 1; the switching output S1 is ON, otherwise OFF
If measured value > threshold 2; the switching output S2 is ON, otherwise OFF