WIKA operating instructions temperature transmitter T12

6. Commissioning, operation

6.3 Connection of programming adapter (PU348)

WARNING!

Configure the transmitter, the programming adapter

and the PC outside the hazardous area.

Yellow and green are connected only if configuration

of the T12 is to be made when the transmitter is

on-line.

For parameterisation in the workshop, no additional

power supply is required; The power is supplied via

a 9 V battery built in to the Programming Adapter

(Programming Unit).

6.3.1 Connection head mounting version T12.10.xxx

Power

supply

Input

red

Disconnect

black

yellow *

green *

T12.10

PU384

32144338X

The connection should be made in accordance with the above

diagram. The red crocodile clip must be connected to the positive

terminal of the transmitter, while the black crocodile clip must be

connected o the negative terminal of the transmitter. The green

and yellow crocodile clips only need to be connected where the

measuring signal should be further transmitted to a connected

evaluation system.