WIKA operating instructions temperature transmitter T12

8.1 Model overview and their European approvals

Model

Ex protection and

Approval No.

Ignition

protection type

head

mounting

version

rail

mounting

version

T12.1x.xx2 T12.30.xx2 II 1G EEx ia IIB/IIC T4/T5/T6

DMT 98 ATEX E 008 X

intrinsically safe

equipment

T12.10.xx9 T12.30.xx9 II 3G Ex nL IIC T4/T5/T6

energy-limited

equipment

II 3G Ex nA IIC T4/T5/T6

non-sparking

equipment

II 3G Ex ic IIC T4/T5/T6

intrinsically safe

equipment

8.2 Special conditions for safe use

T12.30.xxx:

The surface of the case is not conductive. The temperature transmitter

must be mounted in a way that electrostatic charges will not occur.
T12.xx.xx2:

Temperature transmitters in a hazardous area are supplied only

with associated intrinsically safe apparatus that are approved for

this hazardous area. These transmitters must be mounted in a case

that must at least correspond to following ingress protection IP 20

according to EN 60529 / IEC 60529.
T12.10.xx2 for category II 1G/IIC in addition:

The surface of the case is not conductive. The temperature transmitter

must be mounted in a way that electrostatic charges will not occur.
T12.xx.xx9 (Use as energy-limited equipment II 3G EEx nL):

The supply current circuit must fulfil the requirements for ignition

protection type II 3G EEx nL energy-limited per EN 50021. These

temperature transmitters must be mounted in a case that must at

least correspond to following ingress protection IP 54 according to

EN 60529 / IEC 529.