6.3 Anzeigeelemente
6.3.1 Status Anzeige
In der Bushaube befindet sich eine DUO LED (grün/rot) die nach EtherCAT Indicator Specification V0.91
arbeitet.
DUO-LED grün RUN Status
RUN State
Status
Beschreibung
Kategorie
Off
INIT
The device is in state INIT
Mandatory
Blinking
PRE-OPERATIONAL
The device is in state PRE-OPERATIONAL
Mandatory
Single Flash
SAFE-OPERATIONAL
The device is in state SAFE-OPERATIONAL
Mandatory
On
OPERATIONAL
The device is in state OPERATIONAL
Mandatory
Flickering
INITIALISATION or
BOOTSTRAP
The device is booting and has not yet entered the INIT
state, or the device is in state BOOTSTRAP.Firmware
download operation in progress
Optional
Double Flash
Reserved
Reserved for future use
reserved
Triple Flash
Reserved
Reserved for future use
reserved
Quadruple
Reserved
Reserved for future use
reserved
DUO-LED rot ERR Status
ERR State
Fehler
Beschreibung
Beispiel
Kategorie
Off
No error
The EtherCAT
communication of the
device is in working
condition
Mandatory
Flickering
Booting Error
Error was detected. INIT
state reached, but
Parameter "Change" in the
AL status register is set to
0x01:change error
Checksum Error in Flash
Memory.
Optional
Blinking
Invalid Configuration
General Configuration Error
State change commanded
by master is impossible due
to register or object settings.
Mandatory
Single Flash
Unsolicited State
Change
Slave device application
has changed the EtherCAT
state autonomously:
Parameter "Change" in the
AL status register is set to
0x01:change/error.
Synchronisation Error,
device enters Safe-
Operational automatically.
Mandatory
Double Flash
Application Watchdog
Timeout
An application watchdog
timeout has occurred.
Sync Manager Watchdog
timeout
Mandatory
Triple Flash
Reserved
Reserved for future use
Reserved
Quadruple Flash Reserved
Reserved for future use
Reserved
On
PDI Watchdog
Timeout
A PDI Watchdog timeout
has occurred
Application controller is not
responding any more
Optional
6.3.2 Link/Activity Anzeige
Jeweils eine grüne LED für Ein- und Ausgang
Link
Activity
State of Link/Activity indicator
Yes
No
On
Yes
Yes
Flickering
No
Not applicable
Off
Hinweis: alle LED´s sind aus, wenn der Drehgeber an Betriebsspannung liegt, aber noch keine Ethernet-
Verbindung besteht.