12 error code 0x0019, 13 error code 0x001a – BECKHOFF EL9xxx Benutzerhandbuch

Seite 82

Advertising
background image

Anhang

Description

The slave application cannot provide valid input values

Example: A certain hardware which needs to be connected to the slave was disconnected

Current State (or state change)

O, S→O

Resulting state

S + E

Solution

n/a

7.4.12

Error Code 0x0019

Meaning

No valid outputs available

Description

The slave application cannot recieve valid output values.

Example: The slave has a RxPdoToggle output or an “Output Valid” information in its process data. The
RxPdoToggle does not toggle or the OutputValid is not true. Therefore the slave has no process data which
the application can use. If supported, check the RxPDO Toggle Failed Counter in object 0x1C3x.0E). Also,
the Synchronization may have problems (see object 0x10F1:SI2 Sync Error Counter Limit) so that process
data are received too late by the slave so that the local slave cycle misses the toggle event. Another reason
can be that the PLC stopped working

Current State (or state change)

O, S→O

Resulting state

S + E

Solution

The RxPdoToggle may need to be handled by the PLC program

The outputs valid may have to be set by the PLC program

PLC may have stopped, restart PLC

7.4.13

Error Code 0x001A

Meaning

Synchronization error

EL9xxx

82

Version 3.1