7.4.18

Error Code 0x001F

Meaning

Invalid Watchdog Configuration

Description

The Watchdog is configured in the ESC register 0x0400 and 0x0420. EtherCAT defines default watchdog
settings (100ms) or they are defined in the ESI file. If the slave does not accept a change of the expected
settings it returns this AL Status Code Example: A slave may not accept that the WD is deactivated.

Current State (or state change)

O, S, O, P→S

Resulting state

P + E

Solution

Use default WD settings

7.4.19

Error Code 0x0020

Meaning

Slave needs cold start

Description

Slave device require a power off ­ power on reset

Current State (or state change)

Any

Resulting state

Current State + E

Solution

n/a

7.4.20

Error Code 0x0021

Meaning

Slave needs INIT

Description

Slave application requests INIT state

EL9xxx

85