Manual_CANopen_StrainLink_EN_V3_05.doc

33/65

Baumer

22.07.11/dam

Frauenfeld, Switzerland

6.2.2

Restore default parameters

With object 1011h, the factory settings can be loaded. In this process all parameters, except the
communication parameters (Baud rate, Identification), will be set to default values.
For the parameters and the corresponding values, see the start of Section 6.2.


Function mode:















Loading the data takes place when the index 1011h with the “load” message in ASCII code on sub-index 1 is
sent. The message thus has the following structure:

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

600h + ID

8

22h

11h

10h

01h

6Ch

6Fh

61h

64h


Response from CANopen strain link:

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

580h + ID

8

60h

11h

10h

01h

0

0

0

0


Loading the default values means that the values are loaded into RAM. If the values are to remain at the
next reset, the parameters must be stored in EEPROM using the index 1010h.

If you do not store the setting,
the “old” parameters will be
reloaded and activated after the
next Reset

Boot up Message

Factory settings

Old Parameter
activ

Parameter store

(Index 1010)

PWR-On Reset /

NMT Reset

Restore default

(Index 1011)