9. Priorities at data collision (PLC has higher priority)


The PLC transmitter has a higher priority, and the HBLS transmitter has a lower priority.

In case of a collision, which means the HBLS recognises an incoming STX character from
the PLC while sending its own STX to the PLC at the same time, the data, intended to
transfer to the PLC will be interrupted and the data from the PLC will be handled first. When
completed, the data transfer from the HBLS to the PLC will be repeated.


Example of possible collisions:


HBLS is sending push button changed

STX

DLE ??

PLC is sending “LED 1 ON”

STX

DLE ??



Solution:


HBLS is sending push button changed

STX DLE

DLE STX

PLC is sending “LED 1 ON”

STX

31H DLE ETX BCC