2 measuring circuit monitoring, 3 analog output, Measuring circuit monitoring – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Operating Manual Benutzerhandbuch

Seite 100: Analog output, 8 technical data, 2 measuring circuit monitoring 8.3 analog output

Advertising
background image

8 Technical Data

2014-06-12

38

8.2

Measuring circuit monitoring

8.3

Analog output

RTD temperature probe
and KTY11-6

Double thermo-
couples

Thermo-
couples

Current 0 ... 20 mA, 4 ... 20mA
Voltage 0 ... 10 V, 2 ... 10 V

Overrange
and underrange

is detected
LED K1 and KV are lit; "9999“ flashes in the display

Probe and
wire break

is detected
LED K1 and KV are lit; "9999“ flashes in the display; relay output
K1 is inactive

is detected at 4…20mA

and 2…10V

LED K1 and KV are lit;
"9999“ flashes in the display

Relay output K1 is inactive

Probe short-circuit

is detected
LED K1 and KV are lit; "9999“ flashes in the display;
relay output K1 is inactive

is not de-
tected

Type of sig-
nal

Accuracy

Residual ripple

Load influence Temperature coeffi-

cient

Load resistance

Current

4 ... 20 mA

0.5 %

± 0.5 %

± 0.01 mA

80 ppm/K

500

Ω

0 ... 20 mA

Voltage

2 ... 10 V

0.5 %

± 0.5 %

± 15 mV

80 ppm/K

÷

500

Ω

0 ... 10 V

Advertising