8 technical data, 1 analog inputs, Technical data – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Operating Manual Benutzerhandbuch
Seite 98: Analog inputs
Advertising
![background image](/manuals/563577/98/background.png)
8 Technical Data
36
8 Technical
Data
8.1
Analog inputs
RTD temperature probe
Thermocouples
Designation
Measuring range
Accuracy
1
Pt 100
DIN EN 60751
-200 … +850°C
0.1%
KTY11-6
PTC
-50 ... +150 °C
1%
Pt 1000
DIN EN 60751
-200 … +850°C
0.1%
Connection type
2-wire, 3-wire circuit
Measuring range
210
ms
Input filter
digital filter, 2st priority; filter constant can be set from 0 … 100s
Particularities
2xPt100 for differential value calculation, display can also be programmed in °F
Designation
Measuring range
Accuracy
1
Fe-CuNi „L“
DIN 43710
-200 … +900°C
0.4%
Fe-CuNi „J“
DIN EN 60584
-200 … +1200°C
0.4%
Cu-CuNi „U“
DIN 43710
-200 … +600°C
0.4%
Cu-CuNi „T“
DIN EN 60584
-200 … +400°C
0.4%
NiCr-Ni „K“
DIN EN 60584
-200 … +1372°C
0.4%
Advertising