4 Electrical connection
14
Analog inputs
(6.2)
(6.3)
Thermocouple/
Double thermocouple
(safety tested)
(6.5)
RTD temperature probe in 2-wire circuit
(safety tested)
or KTY11-6 PTC in 2-wire circuit
(6.4)
RTD temperature probe in 3-wire circuit
(safety tested)
(6.6)
RTD temperature probe 2 x Pt100 in
2-wire circuit for differential value calculation (no lead compensation possible)
INP (terminal 22 and 21)
IN2 (terminal 21 and 20)
(6.1)
0... 20 mA
4 ... 20 mA (safety tested)
0(2) ... 10 V
Binary input
(5.1)
for connection to potential-free contact
Analog output
(extra code)
(4)
configurable:
0... 20 mA, 4 ... 20 mA (ex-factory), 0 ... 10 V or 2 ... 10 V
Relay output KV
(1)
Relay (N/O) without shroud
Relay output K1
(2)
Relay (change-over contact element) with fuse cut-out
A
Enter the lead resistance for RTD temperature probes in 2-wire circuit when
using greater line lengths.
v
Setup program:
edit=> extended configuration