7 Configuration level

2014-06-12

22

7.1

C111 Analog inputs

Analog input

Remark

Setting range for AL:
(can be restricted via
the set-up)

Limits for
underrange /
overrange

001

Pt 100
DIN EN 60751

in 3-wire circuit

-1999 ... +9999°C

-205°C/ +855°C

006

Pt 1000
DIN EN 60751

in 3-wire circuit

-1999 ... +9999°C

-205°C/ +855°C

601

KTY11-6 PTC

Probe in 2-wire circuit

-1999 ... +9999°C

-55°C/ +155°C

003

Pt 100
DIN EN 60751

in 2-wire circuit

-1999 ... +9999°C

-205°C/ +855°C

005

Pt 1000
DIN EN 60751

in 2-wire circuit

-1999 ... +9999°C

-205°C/ +855°C

024

2x Pt 100 DIN

for differential value calculation

-1999 ... +9999°C

-205°C/ +855°C

The device can calculate a differential value of 2 RTD temperature probes Pt 100 in 2-wire
circuit.
The measuring input INP (terminals 22 and 21) detects the first temperature.
The second measuring input IN2 (terminals 21 and 20) detects the second temperature.

Setting range for ALD: -1999 ... 9999

k

ex-factory

H

The "direct" and "inverse" settings do not influence the switch-
ing behavior of relay K1 during differential value calculation.