7 Configuration level

27

2014-06-12

1

Direct
(S-Function)

If the AL limit value is gone below, the installed relay output K1 switches OFF. The K1 LED is
lit red and the set display value flashes (e.g. INP).
For the temperature limiter, relay output K1 remains in this status even when the measured
value exceeds the limit value AL. Only when the "Reset" key is pressed >3sec or a switch is
activated when the binary input is respectively configured, does the relay output K1 switch on
again and the OK LED is lit green.
The temperature monitor automatically switches the K1 relay output ON and the OK LED is
lit green, when the measured value exceeds the limit value AL.

A

The pre-alarm (UA) is factory-set as an "Absolute value" (C119 = 1) and is responsive to INP and IN2!
If one of the two measured values exceeds the pre-alarm, the KV LED is lit and the KV relay output switches.

Switching
behavior

Remark

Pre alarm range

Alarm range

valid range

Relay output KV
LED KV lights up yellow

active

Relay output KV inaktive
LED KV off

ALLO

Relay inaktive
LED K1 lights up red

Relay K1 aktive

Limit Value

AL

Measured Value

LED OK

green

lights up

Pre alarm

ALHI

Hys1

Hys2

S

P

Ö

3,15A

5

7

6

S

P

5

7

6

Ö

3,15A

Measured Value