15 error messages, Error messages, Chapter 15 „error messages – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Operating Manual Benutzerhandbuch
Seite 115

15 Error messages
53
15 Error
messages
Error display (Err)
Cause
Remedy
The limit value for relay alternations is
exceeded.
h
Increase the limit value for the relay alternations.
v
Chapter 7.11 „C 120 Limit value for relay alterna-
tions“
h
Use the Reset key (press >3sec) for acknowl-
edgement.
v
Chapter 7.12 „C 121 Counter reading for relay
alternations“
0002
Terminal temperature
is outside the range -10...80°C
h
Check ambient temperatures
h
Use the Reset key (press >3sec) for acknowl-
edgement.
If the error cannot be remedied, send the device in.
0003
Reference voltage
The measured value either exceeds 999 or
goes below -999 and is outside the 3-digit
display range.
-
A/D converter error
h
Use the Reset key (press >3sec) to acknowledge
If the error cannot be remedied, send the device in.
0004
Calibration constant
The device must be repaired by JUMO.
h
Send in the device.
v
Chapter 2.1 „Service addresses“
0005
Configuration data
Value cannot be displayed (too high or too
low)
0006
reserved
-
0007
reserved
-