15 Error messages

53

2014-06-12

15 Error

messages

Error display (Err)

Cause

Remedy

The limit value for relay alternations is
exceeded.

h

Increase the limit value for the relay alternations.

v

Chapter 7.11 „C 120 Limit value for relay alterna-
tions“

h

Use the Reset key (press >3sec) for acknowl-
edgement.

v

Chapter 7.12 „C 121 Counter reading for relay
alternations“

0002

Terminal temperature
is outside the range -10...80°C

h

Check ambient temperatures

h

Use the Reset key (press >3sec) for acknowl-
edgement.

If the error cannot be remedied, send the device in.

0003

Reference voltage
The measured value either exceeds 999 or
goes below -999 and is outside the 3-digit
display range.

-

A/D converter error

h

Use the Reset key (press >3sec) to acknowledge

If the error cannot be remedied, send the device in.

0004

Calibration constant

The device must be repaired by JUMO.

h

Send in the device.

v

Chapter 2.1 „Service addresses“

0005

Configuration data
Value cannot be displayed (too high or too
low)

0006

reserved

-

0007

reserved

-