13 Setup program

2014-06-12

50

13.5 2x Pt100 for differential value calculation with prefix

Differential value calculation with prefix is factory set.

-200°C

300°C

AL = 150°C (inverse)

0°C

200°C

100°C

-100°C

300°C

200°C

100°C

0°C

-100°C

-200°C

ALD = 50°C

IN2

INP

valid

range

valid

range

Hys1

Hys1

All difference values diF = INP-IN2 are shown in the picture.
Inside the valid range (green) all values are smaller than the
setting for the difference ALd = 50.

INP = 101°C, IN2 = 50°C
101 - 50 = 51 exceeds Ald = 50 and lies out of the valid range.

INP = 50°C, IN2 = 50°C
50 - 50 = 0 and lies inside the valid range.

Example 1:

Example 2:

The area between the dot and dash lines indicate
the span of the hysteresis (factory setting: 1K)

he inputs INP and IN2 are additionally monitored

in regards to the limit value AL=150°C

T

50°C

1

2