7 Configuration level

2014-06-12

26

7.5

C115 Switching behavior

Switching
behavior

Remark

0

Inverse
(O-Function)

If the AL limit value is exceeded, the installed relay output K1 switches OFF. The K1 LED is lit
red and the set display value flashes (e.g. INP).
For the temperature limiter, relay output K1 remains in this status even when the measured
value drops below the limit value AL. Only when the "Reset" key is pressed >3sec or a switch
is activated when the binary input is respectively configured, does the relay output K1 switch
on again and the OK LED is lit green.
The temperature monitor automatically switches the K1 relay output ON and the OK LED is
lit green, when the measured value drops below the limit value AL.

k

ex-factory

ALLO

AL

ALHI

Hys1

Hys2

S

P

Ö

3,15A

5

7

6

S

P

5

7

6

Ö

3,15A

Relay output KV
LED KV lights up yellow

active

Relay output KV inaktive
LED KV off

Relay inaktive
LED K1 lights up red

Relay K1 aktive
LED OK

green

lights up

Pre alarm range

Pre alarm

Measured Value

Measured Value

Limit Value

Alarm range

Valid range