8 c118 display shut-down after timeout, 9 c119 pre-alarm function, C118 display shut-down after timeout – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Operating Manual Benutzerhandbuch

Seite 91: C119 pre-alarm function, 7 configuration level

Advertising
background image

7 Configuration level

29

2014-06-12

7.8

C118 Display shut-down after timeout

7.9

C119 Pre-alarm function

The pre-alarm signal is indicated by the KV LED and put out simultaneously on the relay output KV. The switching behavior can
be configured as an absolute value or distance to the limit value (relative).

k

ex-factory

Display shut-down

Remark

0

inactive

The display is permanently switched on.

1

active

Display switches off after timeout and reappears
as soon as a key is pressed.
If an alarm or error message occurs, it is immediately displayed although
the display is shut down.

v

Chapter 14 „Alarm messages“

v

Chapter 15 „Error messages“

Pre-alarm function

Remark

0

no function

Pre-alarm and LED KV is switched off.

1

Absolute value

The value for the pre-alarm (UA) is defined fixed and is independent of
the set limit value.

2

Distance to the limit value

The value for the pre-alarm (UA) automatically changes according to the
set limit value and is above or below the limit value depending on the
switching behavior.

Advertising