2 c112 setting for double thermocouple, 3 c113 unit, decimal places, 4 c114 device function – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Operating Manual Benutzerhandbuch
Seite 87: C112 setting for double thermocouple, C113 unit, decimal places, C114 device function, 7 configuration level

7 Configuration level
25
7.2
C112 Setting for double thermocouple
Only available if C111 is set to 037 ... 048.
v
Chapter 7.1 „C111 Analog inputs“
7.3
C113 Unit, decimal places
7.4
C114 Device function
Double thermocouple
Remark
0
no
Probe short-circuit is not detected!
1
yes
Can detect a probe short-circuit
Unit, decimal places
Remark
0
°C, no digit after the decimal point
1
°C, one digit after the decimal
point
2
°F, no digit after the decimal point
3
°F, one digit after the decimal point
Device function
Remark
0
Initial commissioning/start-up of TB
Temperature limiters
The TB remains locked when the mains connection is reactivated indepen-
dent of the switching status of the relay output K1 prior to the mains failure.
1
Temperature limiter TB
Unlocking only required when the temperature is exceeded
2
Temperature monitor TW
automatic unlocking
A
When converting the unit to °F, the measured value is con-
verted. All other values referring to the measured value, e.g.
AL, are maintained !