2 c112 setting for double thermocouple, 3 c113 unit, decimal places, 4 c114 device function – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Operating Manual Benutzerhandbuch

Seite 87: C112 setting for double thermocouple, C113 unit, decimal places, C114 device function, 7 configuration level

Advertising
background image

7 Configuration level

25

2014-06-12

7.2

C112 Setting for double thermocouple

Only available if C111 is set to 037 ... 048.

v

Chapter 7.1 „C111 Analog inputs“

7.3

C113 Unit, decimal places

7.4

C114 Device function

Double thermocouple

Remark

0

no

Probe short-circuit is not detected!

1

yes

Can detect a probe short-circuit

Unit, decimal places

Remark

0

°C, no digit after the decimal point

1

°C, one digit after the decimal
point

2

°F, no digit after the decimal point

3

°F, one digit after the decimal point

Device function

Remark

0

Initial commissioning/start-up of TB
Temperature limiters

The TB remains locked when the mains connection is reactivated indepen-
dent of the switching status of the relay output K1 prior to the mains failure.

1

Temperature limiter TB

Unlocking only required when the temperature is exceeded

2

Temperature monitor TW

automatic unlocking

A

When converting the unit to °F, the measured value is con-
verted. All other values referring to the measured value, e.g.
AL, are maintained !