15 behavior when the scaling range is exceeded, 7 configuration level – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Operating Manual Benutzerhandbuch

Seite 96

Advertising
background image

7 Configuration level

2014-06-12

34

7.15 Behavior when the scaling range is exceeded

The standard signal range of the analog output is limited as follows as per recommendation of Namur NE 43:

Type of signal lower

limit

upper
limit

0: 4 ... 20 mA

3.8 mA

20.5 mA

1: 0 ... 20 mA

0 mA

20.5 mA

2: 2 ... 10 V

1.8 V

10.2 V

3: 0 ... 10 V

0 V

10.2 V

k

ex-factory

Measured value

Standard Signal
for Analog output

4 mA

20 mA

= 0 °C

= 100 °C

3,8 mA

20,5 mA

Advertising