7 Configuration level
34
7.15 Behavior when the scaling range is exceeded
The standard signal range of the analog output is limited as follows as per recommendation of Namur NE 43:
Type of signal lower
limit
upper
limit
0: 4 ... 20 mA
3.8 mA
20.5 mA
1: 0 ... 20 mA
0 mA
20.5 mA
2: 2 ... 10 V
1.8 V
10.2 V
3: 0 ... 10 V
0 V
10.2 V
k
ex-factory
Measured value
Standard Signal
for Analog output
4 mA
20 mA
= 0 °C
= 100 °C
3,8 mA
20,5 mA