7 Configuration level

23

2014-06-12

During the differential value calculation, the measured value INP, IN2 and the set differential value ALD are evaluated.
The relay output K1 is active and the OK LED is lit green as long as the system is within the valid range.
If the system leaves the valid range the relay output K1 switches off and the K1 LED is lit red.

Analog input

Remark

Setting range for AL:
(can be restricted via
the set-up)

Limits for
underrange /
overrange

-200°C

300°C

AL = 150°C (inverse)

0°C

200°C

100°C

-100°C

300°C

200°C

100°C

0°C

-100°C

-200°C

ALD = 50°C

IN2

INP

valid

range

valid

range

Hys1

Hys1

All difference values diF = INP-IN2 are shown in the picture.
Inside the valid range (green) all values are smaller than the
setting for the difference ALd = 50.

INP = 101°C, IN2 = 50°C
101 - 50 = 51 exceeds Ald = 50 and lies out of the valid range.

INP = 50°C, IN2 = 50°C
50 - 50 = 0 and lies inside the valid range.

Example 1:

Example 2:

The area between the dot and dash lines indicate
the span of the hysteresis (factory setting: 1K)

he inputs INP and IN2 are additionally monitored

in regards to the limit value AL=150°C

T

50°C

1

2

v

Change-over to absolute

value measurement:
Chapter 13 „Setup program“