7 Configuration level

2014-06-12

30

7.10 SCL, SCH, ALLO, ALHI, OFFS, HYS1, HYS2

Remark

Value range

(ex-factory
setting bold)

Lower display value when standard
signals are connected.

only appears when C111 is set to 52, 53, 63 or
71 (current, voltage)

-1999 ... 0 ... +9999

Upper display value when standard
signals are connected.

-1999 ... 100 ... +9999

Lower limit of the setting range for
limit value AL

This can be used to limit the setting range!
adjustable: max. -1999 ... 9999

-1999 ... +9999

Upper limit of the setting range for
limit value AL

-1999...+9999

Measured value offset

The measured value offset can be used to cor-
rect a measured value by a programmable
value.

-1999 ...0... +9999

Hysteresis in respect to the limit
value AL

0 ... 100

0...1... 100

Hysteresis in respect to the pre-alarm
UA

0 ... 100 (only if C119 = 1 or C119 = 2)

0...1... 100