8 Technical Data

39

2014-06-12

8.4

Binary input

8.5

Relay outputs

8.6

Voltage supply

8.7

Test voltages as per EN 60730, part 1

Connection

Function

1 potential-free contact

Unlocking, keyboard locking, level locking can be configured

Relay output KV

Relay (N/O) without shroud
Contact rating of 3A /230V, 50 Hz ohmic load

Relay output K1

100000 operations at a performance of 3A /230V, 50Hz resistive load
Contact protection wiring:
Fuse cut-out 3,15AT installed in the device

Voltage supply

AC/DC 20 ... 30V, 48 ... 63Hz,
AC 110...240V, +10/-15%, 48 ... 63Hz

Amperage

< 15 VA

Input and output against voltage supply

- at a voltage supply AC 110 ... 240V +10% /-15%

3.7kV/50Hz

- at a voltage supply AC/DC 20 ... 30V, 48...63 Hz

3.7kV/50Hz