4 binary input, 5 relay outputs, 6 voltage supply – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Operating Manual Benutzerhandbuch
Seite 101: 7 test voltages as per en 60730, part 1, Binary input, Relay outputs, Voltage supply, Test voltages as per en 60730, part 1, 8 technical data
Advertising
![background image](/manuals/563577/101/background.png)
8 Technical Data
39
8.4
Binary input
8.5
Relay outputs
8.6
Voltage supply
8.7
Test voltages as per EN 60730, part 1
Connection
Function
1 potential-free contact
Unlocking, keyboard locking, level locking can be configured
Relay output KV
Relay (N/O) without shroud
Contact rating of 3A /230V, 50 Hz ohmic load
Relay output K1
100000 operations at a performance of 3A /230V, 50Hz resistive load
Contact protection wiring:
Fuse cut-out 3,15AT installed in the device
Voltage supply
AC/DC 20 ... 30V, 48 ... 63Hz,
AC 110...240V, +10/-15%, 48 ... 63Hz
Amperage
< 15 VA
Input and output against voltage supply
- at a voltage supply AC 110 ... 240V +10% /-15%
3.7kV/50Hz
- at a voltage supply AC/DC 20 ... 30V, 48...63 Hz
3.7kV/50Hz