Project example – Lenze VisiWinNet VisiWinNET Smart Benutzerhandbuch
Seite 210

Project example
Configuring the alarm system
Creating alarms
l
210
SHP−VWNS DE/EN 6.1
Alarms for "Grp2" alarm group
3. In order to create the two alarms in alarm group Grp2, select alarm group Grp2 in
Project Explorer, click in the client area with the right−hand mouse button and, in the
context menu, select the New command.
4. Specify the following properties:
Properties for alarms
No. Tab/Property
Value
Comments
3
General
Name
Msg3
Text
MessageSource; Bit 2
See alarms for alarm group "Grp1"
Event variable
MessageSource
Bit No. of event variable
2
Priority
3
Extended
Status variable
MessageState
Bit No.of status variable
8
4
General
Name
Msg4
Text
MessageSource; Bit 3
See alarms for alarm group "Grp1"
Event variable
MessageSource
Bit No. of event variable
3
Priority
4
Extended
Status variable
MessageState
Bit No.of status variable
12
In the following, the values indicated above will be used to demonstrate all the aspects of
how the alarm system functions. The "Status variable" parameter is optional. Specification
of an alarm text is highly recommended. Specification of the event variable is obligatory.