3 specifications of the connected flow sensor, 4 electrical connection, Specifications of the connected flow sensor – Burkert Type 8025 Benutzerhandbuch

Seite 15: Electrical connection

Advertising
background image

13

Technicaldata

6.3.3

Specifications of the connected flow sensor

Signal originating from the remote sensor

• type

• frequency

• max. voltage

• pulse, sine-wave (typical sensitivity 50 mV peak-

to-peak at 250 Hz), "on/off", or standard voltage
0-5 V DC

• 0,6 Hz to 2,2 kHz, can be adjusted

• 36 V DC

Input impedance

depends on the position of selector "LOAD" on the
electronic board of the 8025. See chap. “7.4.10”

Power supply

supplied by the transmitter depending on the position
of selector "SENSOR SUPPLY" of the 8025, either:

• 5 V DC, 30 mA max.

• (L+)-12V: supply voltage (L+) of the transmitter

minus 12 V DC (minus 12,5 V DC max.), 80 mA max.

• L+: supply voltage (L+) of the transmitter (minus

1,5 V DC max.), 140 mA max. (if the device is ener-
gized with 12-36 V DC), 80 mA max. (if the device is
energized with 115/230 V AC)

6.3.4

Electrical connection

Type of connection

on the terminal blocks of the electronics (and through
cable glands M16x1,5, for the wall-mounted versions)

Cable specifications

• cable type

• Cross section of wires

• Diameter of each cable (for the cable glands

M16x1,5 of the wall-mounted version)

• shielded

• 0.2 to 1.5 mm

2

• 4 to 8 mm

English

Type 8025 UNIVERSAL