Operatingandcommissioning

8.6.12 configuring the relay outputs Do2 and Do3 to switch a

load depending on two thresholds

The hysteresis or window operation is detailed in “Figure 39”, chap. “8.6.8”.

OUtPUt

DO2

hYStERES.

DO3

2-= 0.000

2+= 0.000

Enter a flow rate value

1)

, associated to the high

threshold, in the unit chosen in the "UNIT" parameter.

Confirm.

wiNDOw

Enter a flow rate value

1)

, associated to the low

threshold, in the unit chosen in the "UNIT" parameter.

Confirm.

iNV YES

iNV NO

0......9

Choose the operating, inverted or not inverted, of the
relay output.

DEL. 2= 00

Enter the delay before switching (value between 0
and 99 s).

Confirm.

Configure the DO3 relay out-

put the same way as the DO2

relay output.

1)

If hysteresis operating: Value set for 2- respectively 3- ≤ Value set for 2+ respectively 3+.

If window operating: Value set for 2- respectively 3- < Value set for 2+ respectively 3+.

Figure 42:

Configuration of the DO2 or DO3 relay output with switching thresholds