3 wiring a panel version, 4 wiring a wall-mounted version, Wiring a panel version – Burkert Type 8025 Benutzerhandbuch

Seite 23: Wiring a wall-mounted version

Advertising
background image

21

Installationandwiring

7.4.3

Wiring a panel version

Only move the selectors when the power supply is off.

Install the device as described in chap. “7.2”.

Set the selectors "SENSOR TYPE", "SENSOR SUPPLY" and "LOAD": see chap. “7.4.10”.

Before wiring the device insert the supplied cable clips into the slots of
the electronic board.

Figure 11:

Inserting the cable clips

Wire acc. to chap. “7.4.5” , “7.4.6”, “7.4.9” and “7.4.10”.

Secure the power supply cable, the flow sensor connection cable and, depending on the version, the relay
connection cables, with the cable clips.

7.4.4

Wiring a wall-mounted version

Only move the selectors when the power supply is off.

Insert the supplied stopper gaskets into the unused cable glands to ensure the tightness of the device.

• Unscrew the unused cable gland.

• Remove the transparent disk.

• Insert the supplied stopper gasket.

• Screw the nut of the cable gland.

Install the device as described in chap. “7.3”.

Set the selectors "SENSOR TYPE", "SENSOR SUPPLY" and "LOAD": see chap. “7.4.10”.

If the wall-mounted version is energized with a 115/230 V AC power supply, set selector E as shown in
“Figure 12”.

English

Type 8025 UNIVERSAL

Advertising