36 v dc – Burkert Type 8025 Benutzerhandbuch

Seite 26

Advertising
background image

24

Installationandwiring

7.4.6

Wiring the Do1 transistor output of a panel version or a
wall-mounted version, 12-36 V Dc

Insert the supplied stopper gaskets into the unused cable glands to ensure the tightness of the device.

• Unscrew the unused cable gland.

• Remove the transparent disk.

• Insert the supplied stopper gasket.

• Screw the nut of the cable gland.

PE

PE

PE

L+

L-

PE P- P+

NC

Iout

PULSE

DO1

Supply

12..36Vdc

Univ

Batch

(AO1)

300 mA

+

-

12-36 V DC

(*)

+

-

+

- 5-36 VDC

PLC

Power supply of

the device

Power supply of

the device

PLC

PE

PE

PE

L+

L-

PE P- P+

NC

Iout

PULSE

DO1

Supply

12..36Vdc

Univ

Batch

(AO1)

300 mA

(*)

+

-

+

- 5-36 VDC

+

-

12-36 V DC

*) If a direct earth connection is not possible, fit a 100 nF/50 V capacitor between the negative power supply terminal and
the earth

Figure 18:

NPN wiring of the DO1 transistor output

Figure 19:

PNP wiring of the DO1 transistor output

7.4.7

Wiring the Ao1 current output of a wall-mounted version,
115/230 V Ac

Insert the supplied stopper gaskets into the unused cable glands to ensure the tightness of the device.

• Unscrew the unused cable gland.

• Remove the transparent disk.

• Insert the supplied stopper gasket.

• Screw the nut of the cable gland.

Only move the selectors when the power supply is off.

The 4-20 mA output can be wired in either sourcing or sinking mode.

English

Type 8025 UNIVERSAL

Advertising