Installationandwiring

Table 1:

Position of selectors "SENSOR TYPE" and "LOAD" and terminal assignment of terminal block "FLOW
SENSOR" depending on the signal emitted by the flow sensor

Type of signal
emitted by the
flow sensor

Selector

"SENSOR

TYPE"

( D )

Selector

"SENSOR

SUPPLY"

( B )

Selector "LOAD"

C

LOAD

COIL/PNP

39K

470

2.2K

Terminal assignment of

terminal block "FLOW

SENSOR"

FLOW

SENSOR

SUPPLY

NC

COIL

PULSE INPUT

NPN/PNP

2

1

3

PE

+

-

sinusoid (coil)

Set the
selector
on "COIL"
(“Figure
25”)

Any
position.

Set selector "LOAD" on
"39K": the input impedance
on terminals 1 and 2 of
terminal block "FLOW
SENSOR" will then be
39 kW

2

1

3 PE

NC

39 kΩ

8025

Flow sensor

pulse, PNP

Set the
selector on
"NPN/PNP"
(“Figure
25”)

Set the
selector as
shown in
“Figure 26”.

Set selector "LOAD" on
"39K": the input impedance
on terminals 1 and 2 of
terminal block "FLOW
SENSOR" will then be
39 kW

2

1

3 PE

39 kΩ

8025

Flow sensor

English

Type 8025 UNIVERSAL