Installationandwiring

Type of signal
emitted by the
flow sensor

Selector

"SENSOR

TYPE"

( D )

Selector

"SENSOR

SUPPLY"

( B )

Selector "LOAD"

C

LOAD

COIL/PNP

39K

470

2.2K

Terminal assignment of

terminal block "FLOW

SENSOR"

FLOW

SENSOR

SUPPLY

NC

COIL

PULSE INPUT

NPN/PNP

2

1

3

PE

+

-

0-5 V DC
standard
voltage signal
(TTL, for
example)

Set the
selector on
"NPN/PNP"
(“Figure
25”)

Set the
selector as
shown in
“Figure 26”.

Set selector "LOAD" on
"39K": the input impedance
on terminals 1 and 2 of
terminal block "FLOW
SENSOR" will then be
39 kW

2

1

3 PE

39 kΩ

8025

Flow sensor

pulse, NPN

Set the
selector on
"NPN/PNP"
(“Figure
25”)

Set the
selector as
shown in
“Figure 26”.

Set selector "LOAD":

• either on "2.2k": the load

resistance R is then 2,2 kW

• either on "470": the load

resistance R is then 470 W

2

1

3 PE

8025

R

+3 V

Flow sensor

English

Type 8025 UNIVERSAL