32

Installationandwiring

Type of signal
emitted by the
flow sensor

Selector

"SENSOR

TYPE"

( D )

Selector

"SENSOR

SUPPLY"

( B )

Selector "LOAD"

C

LOAD

COIL/PNP

39K

470

2.2K

Terminal assignment of

terminal block "FLOW

SENSOR"

FLOW

SENSOR

SUPPLY

NC

COIL

PULSE INPUT

NPN/PNP

2

1

3

PE

+

-

"on/off" signal
(Reed relay for
example)

Set the
selector on
"NPN/PNP"
(“Figure
25”)

Set the
selector as
shown in
“Figure 26”.

Set selector "LOAD":

• either on "2.2k": the load

resistance R is then 2,2 kW

• either on "470": the load

resistance R is then 470 W

2

1

3 PE

8025

R

+3 V

...

Flow sensor

Table 2:

Default positions of selectors "SENSOR SUPPLY", "LOAD" and "SENSOR TYPE"

Selector

Default position

SENSOR SUPPLY ( B )

L+

LOAD ( C )

2.2KOhms

SENSOR TYPE ( D )

NPN/PNP