Maintenanceandtroubleshooting

9.3.5

Resolution of problems without message generation and
with device status LED green

Device
status
leD

current
output
Ao1

output Do1
and/or Do2
and/or Do3

possible cause

recommended action

green

4-20 mA depending on

the thresholds or
switched

1)

The device does not properly
measure the flow rate.

Check that the K factor corre-
sponds to the fitting used.

Carry out a Teach-In procedure
to determine the K factor of the
fitting used.

green

4-20 mA depending on

the thresholds or
switched

1)

The displayed flow rate is not
nil but the flow rate in the pipe
is.

Check that the flow rate in the
pipe is nil.

Check the filter chosen. See chap.
“8.6.14”.

green

4-20 mA depending on

the thresholds or
switched

1)

The displayed flow rate is
always nil.

Check that the flow rate in the
pipe is not nil.

Check that the entered K factor is
correct, and

Choose a smaller flow rate unit or
increase the number of displayed
decimals.

green

4-20 mA depending on

the thresholds or
switched

1)

The displayed flow rate is not
stable.

Check that there is fluid in the pipe.

Choose a higher filter value.

green

4-20 mA depending on

the thresholds or
switched

1)

The displayed flow rate
changes very slowly.

Check that there is fluid in the pipe.

Choose a lower filter value.

1)

If the output is configured to switch when a warning message is generated. See chap. 8.6.5.