Burkert Type 8025 Benutzerhandbuch

Seite 59

Advertising
background image

57

Operatingandcommissioning

DEL.= 00

Enter the value of the time delay (value between 0 and 99 s) one or
the other threshold can be exceeded before a warning message is
generated by the device.

Confirm.

FLOw-w.

VOLUME-w.

w-= 0.000

w+= 0.000

Enter a flow rate value (in the unit chosen in the "UNIT" parameter)
such as W+ > W-, above which a "WARN HI" warning message is
generated by the device.

Confirm.

Enter a flow rate value (in the unit chosen in the "UNIT" parameter),
below which a "WARN LO" warning message is generated by the
device.

Confirm.

wARNiNG

Figure 53:

Diagram of the "FLOW-W." parameter of the Test menu

To be warned when the flow rate is too low or too high, enter the flow rate range (in the units that have been
chosen in the "UNIT" parameter of the Parameters menu), outside which the device generates a warning
message, "WARN LO" or "WARN HI", and turns the device status LED to orange.

When a warning message, "WARN LO" or "WARN HI", is generated by the device:

check the process.

if the process is not faulty, check the flow sensor condition and clean it if necessary.

if the flow rate measurement is still faulty, contact the Bürkert retailer.

• The transistor output or either relay output can be configured to switch when a warning message is gen-

erated by the device. See chap. 8.6.5.

• See also "If you encounter problems" in chap. “9.3”

If you do not want to adjust another parameter, confirm the "END" parameter to save the settings or not and
go back to the Process level.

English

Type 8025 UNIVERSAL

Advertising