Operatingandcommissioning

OUtPUt

4 = 20.00

AO1

ERR. 22MA.

Enter the flow rate associated to a 4 mA current
value, in the unit chosen in the "UNIT" parameter.

Confirm.

20 = 180.0

Enter the flow rate associated to a 20 mA current
value, in the unit chosen in the "UNIT" parameter.

Confirm.

4MA-20MA

See chap. 8.6.7.

To invert the output signal, give a lower flow rate value to the 20 mA current value than to the 4 mA current
value.

To disable the current output, set both range bounds, 4 and 20 mA, to zero. In this case the output delivers a
constant current of 4 mA.

Figure 34:

Associating a flow rate range to the current output

8.6.7

Activating / Deactivating the emission of a 22 mA current
on the current output

When the device generates an operating fault (see chap. “9.3.2”), the current output can be configured to send
out a 22 mA current even if the current output is deactivated.

OUtPUt

ERR. 22MA.

AO1

DO1

Activate / deactivate the generation of
a 22 mA current on the current output,
when the device generates a fault.

Confirm.

ENABLE

DiSABLE

0......9

Figure 35:

Activating or deactivating the emission of a 22 mA current

If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press

ENTER

to save the settings or not and go back to the Process level.