Message is generated by the device, Configuring the filter of the measured flow rate, Figure 43 ) – Burkert Type 8025 Benutzerhandbuch

Seite 53: Figure 43

Advertising
background image

51

Operatingandcommissioning

8.6.13 configuring the relay outputs Do2 and Do3 to switch a

load when a warning message is generated by the device

When the device generates a warning message, the device status LED is orange.

The generation of a warning message can also be indicated by the switching of the relay output.

Configure the DO3 relay output the

same way as the DO2 relay output.

OUtPUt

DO2

wARNiNG

DO3

iNV YES

iNV NO

0......9

Choose the operating, inverted or not inverted, of the
relay output.

Confirm.

Figure 43:

Configuration of the DO2 or DO3 relay output to indicate the generation of a warning message

8.6.14 configuring the filter of the measured flow rate

This parameter makes it possible to dampen the fluctuations:

• of the display,

• of the AO1 current output.

Ten filters are available.

When the "fast" filter is active and the flow rate varies for ±30 % (for example when charging the pipe or
stopping the flow), the filter is disabled: the new flow rate is immediately taken into account by the device.

If a too high filter is chosen, the device does not detect the sudden flow rate changes thus the flow rate in
the pipe may strongly defer from the displayed flow rate or the flow rate transmitted to the current output.

A sudden stop of the flow is immediately detected whatever filter is active.

FiLtER

FiLtER 0

tOtAL

SLOw

FASt

0......9

Choose the slow or fast filter.

Confirm

Choose the filter number.

Confirm

FiLtER 9

0......9

Figure 44:

Diagram of the "FILTER" parameter of the Parameters menu

English

Type 8025 UNIVERSAL

Advertising