Commissioning

Proline Promass 80 PROFIBUS PA

54

It is essential to adhere to the following sequence/assignment when configuring the modules in the
PROFIBUS master system:

!

Note!
• The assignment of the measured variables for the Analog Input function blocks 1 to 4 and the

Totalizer function block 1 can be changed by means of the CHANNEL function. A detailed
description of the individual modules is contained in the following section.

• The device has to be reset once a new configuration has been loaded to the automation system.

This can be effected as follows:
– By means of the local display
– By means of an operating program (e.g. FieldCare)
– By switching the supply voltage off and on again.

6.6.3

Description of the modules

AI module (Analog Input)

The corresponding measured variable, including the status, is cyclically transmitted to the
PROFIBUS master (Class 1) by means of the AI module (slots 1 to 4). The measured variable is
represented in the first four bytes in the form of floating point numbers in accordance with the
IEEE 754 standard. The fifth byte contains standardized status information corresponding to the
measured variable.
Further information on the device status

→ Page 71

Input data

Slot

sequence

Module

Description

1

AI

Analog Input function block 1
Output variable

→ mass flow (factory setting)

2

AI

Analog Input function block 2
Output variable

→ volume flow (factory setting)

3

AI

Analog Input function block 3
Output variable

→ corrected volume flow (factory setting)

4

AI

Analog Input function block 4
Output variable

→ density (factory setting)

5

TOTAL or

SETTOT_TOTAL or

SETTOT_MODETOT_TOTAL

Totalizer function block 1
TOTAL

→ output variable = totalized mass flow (factory

setting)
SETTOT

→ totalizer control

MODETOT

→ totalizer configuration

6

DISPLAY_VALUE

Default value for local display

7

CONTROL_BLOCK

Control of device functions

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Measured variable (IEEE 754 floating point
number)

Status