Influence of medium pressure, Promass f, m, Promass e – FMC Corporation - Talstar 80 Benutzerhandbuch

Seite 97: Promass a, Promass h

Advertising
background image

Proline Promass 80 PROFIBUS PA

Technical data

97

Influence of medium pressure

The following section shows the effect on accuracy of mass flow due to a difference between
calibration pressure and process pressure.

Promass F, M:

Promass E:

With nominal diameters DN 8 to 40 (3/8" to 1½"), the effect on accuracy of mass flow due to a
difference between calibration pressure and process pressure is negligible.
At DN 50 (2"), the effect is –0.009% o.r. / bar (–0.006% v.M. / psi) (o.r. = of reading).

Promass A:

A difference between calibration pressure and process pressure has no effect on measuring accuracy.

Promass H:

DN

Promass F,

Promass F high-temperature

Promass M

Promass M, high pressure

[% o.r./bar]

[% o.r./psi]

[% o.r./bar]

[% o.r./psi]

[% o.r./bar]

[% o.r./psi]

8

3/8"

No influence

0.009

−0.0006

0.006

0.0004

15

½"

No influence

0.008

−0.0005

0.005

0.0003

25

1"

No influence

0.009

−0.0006

0.003

0.0002

40

1½"

−0.003

−0.0002

0.005

−0.0003

50

2"

−0.008

−0.0005

No influence

80

3"

−0.009

−0.0006

No influence

100

4"

−0.012

−0.0008

150

6"

−0.009

−0.0006

250

10"

−0.009

−0.0006

o.r. = of reading

DN

[% o.r./bar]

[% o.r./psi]

8

3/8"

–0.017

–0.0012

15

½"

–0.021

–0.0014

25

1"

–0.013

–0.0019

40

1½"

–0.018

–0.0012

50

2"

–0.020

–0.0014