CONTROL_BLOCK module

By means of the CONTROL_BLOCK module (slot 7), the measuring device is able to process device-
specific control variables from the PROFIBUS master (Class 1) in cyclic data transmission (e.g.
switching on positive zero return).

Supported control variables of the CONTROL_BLOCK module

The following device-specific control variables can be activated by changing the output byte from
0

→ x:

Example (change the output byte)

Output data

EMPTY_MODULE module

The measuring device is a so-called modular PROFIBUS slave. In contrast to a compact slave, the
structure of a modular slave is variable - it consists of several individual modules. In the GSD file,
the individual modules are described with their individual properties. The modules are permanently
assigned to the slots, i.e. the sequence or arrangement of the modules must be observed when
configuring the modules. Gaps between configured modules have to be assigned the
EMPTY_MODULE module.
For a more detailed description, see

→ Page 54

Module

Control variables

CONTROL_BLOCK

0

→ 2: Positive zero return ON

0

→ 3: Positive zero return OFF

0

→ 4: Run zero point adjustment

0

→ 8: UNIDIRECTIONAL measuring mode

0

→ 9: BIDIRECTIONAL measuring mode

0

→ 24: Run UNIT TO BUS function

!

Note!

The control (e.g. switching on positive zero return) is executed by cyclic data transmission if the output byte switches from
"0" to the bit pattern in question. The output byte must always switch from "0". A switchback to "0" does not have any
effect.

From

To

Result

0

2

Positive zero return is switched on.

2

0

No effect

0

3

Positive zero return is switched off.

3

2

No effect

Byte 1

Control