Commissioning

Proline Promass 80 PROFIBUS PA

60

6.6.4

Configuration examples with Simatic S7 HW-Konfig

Example 1:

a0004775

Fig. 33:

Complete configuration using the Promass 80 GSD file.

It is essential to adhere to the following sequence when configuring the modules in the
PROFIBUS master (Class 1):

Slot

sequence

Module

Byte length

input data

Byte length
output data

Description

1

AI

5

Analog Input function block 1
Output variable

→ mass flow (factory setting)

2

AI

5

Analog Input function block 2
Output variable

→ volume flow (factory setting)

3

AI

5

Analog Input function block 3
Output variable

→ corrected volume flow (factory setting)

4

AI

5

Analog Input function block 4
Output variable

→ density (factory setting)

5

SETTOT_MODETOT_TOTAL

5

2

Totalizer function block 1
TOTAL

→ output variable = totalized mass flow (factory setting)

SETTOT

→ totalizer control

MODETOT

→ totalizer configuration

6

DISPLAY_VALUE

5

Default value for local display

7

CONTROL_BLOCK

1

Control of device functions