4 configuration examples with simatic s7 hwkonfig, Example 1, 4 configuration examples with simatic s7 – FMC Corporation - Talstar 80 Benutzerhandbuch
Seite 60: Hw-konfig, 4 configuration examples with simatic s7 hw-konfig

Commissioning
Proline Promass 80 PROFIBUS PA
60
6.6.4
Configuration examples with Simatic S7 HW-Konfig
Example 1:
a0004775
Fig. 33:
Complete configuration using the Promass 80 GSD file.
It is essential to adhere to the following sequence when configuring the modules in the
PROFIBUS master (Class 1):
Slot
sequence
Module
Byte length
input data
Byte length
output data
Description
1
AI
5
–
Analog Input function block 1
Output variable
→ mass flow (factory setting)
2
AI
5
–
Analog Input function block 2
Output variable
→ volume flow (factory setting)
3
AI
5
–
Analog Input function block 3
Output variable
→ corrected volume flow (factory setting)
4
AI
5
–
Analog Input function block 4
Output variable
→ density (factory setting)
5
SETTOT_MODETOT_TOTAL
5
2
Totalizer function block 1
TOTAL
→ output variable = totalized mass flow (factory setting)
SETTOT
→ totalizer control
MODETOT
→ totalizer configuration
6
DISPLAY_VALUE
–
5
Default value for local display
7
CONTROL_BLOCK
–
1
Control of device functions