Troubleshooting

Proline Promass 80 PROFIBUS PA

70

Network structure

Check permissible fieldbus length and number of spurs.

→ Page 26

Basic current

Is there a basic current of min. 11 mA?

Bus address

Check bus address: make sure there are no double assignments

Bus termination
(Termination)

Has the PROFIBUS network been terminated correctly?
Each bus segment must always be terminated with a bus terminator at both ends (start and
finish). Otherwise there may be interference in communication.

Current consumption,
permissible feed current

Check the current consumption of the bus segment:
The current consumption of the bus segment in question (= total of basic currents of all bus
users) must not exceed the max. permissible feed current of the bus power supply.

System or process error messages

System or process errors which occur during commissioning or operation can be displayed via the local display or an
operating program (e.g. FieldCare) in the ACTUAL SYSTEM CONDITION function.

Other error (without error message)

Some other error has
occurred.

Diagnosis and rectification

→ Seite 79