Profibus pa) – Burkert Type 8635 Benutzerhandbuch
Seite 119

8635 - 117
B
USKOMMUNIKATION
KONFIGURIEREN
(PROFIBUS PA)
* nicht über PDM oder Commuwin verfügbar
N: Non-volatile parameter
S: Static revision counter parameter
D: Dynamic parameter
C: Constant parameter
Parameter
Slot
Index
Index
absol-
ut
Lesen Schrei-
ben
Typ
Größe
Byte
Speicher-
klasse
Transducer Block (Analog Output)
VALVE_MAINT_DATE
1
151
X
X
OSTRING
16
S
SERVO_GAIN_2
1
152
X
X
FLOAT
4
S
TAB_OP_CODE
1
155
X
X
UNSIGNED8
1
D
TAB_STATUS
1
156
X
UNSIGNED8
1
D
POSITIONING_VALUE
1
157
X
DS-33
5
D
FEEDBACK_VALUE
1
158
X
DS-33
5
D
VALVE_MAN
1
159
X
X
OSTRING
16
S
ACTUATOR_MAN
1
160
X
X
OSTRING
16
S
VALVE_TYP
1
161
X
X
OSTRING
1
S
ACTUATOR_TYPE
1
162
X
UNSIGNED8
1
C
ACTUATOR_ACTION
1
163
X
X
UNSIGNED8
1
S
VALVE_SER_NUM
1
164
X
X
OSTRING
16
S
ACTUATOR_SER_NUM
1
165
X
X
OSTRING
16
S
ADD_GEAR_SER_NUM
1
166
X
X
OSTRING
16
S
ADD_GEAR_MAN
1
167
X
X
OSTRING
16
S
ADD_GEAR_ID
1
168
X
X
OSTRING
16
S
ADD_GEAR_INST_DATE
1
169
X
X
OSTRING
16
S
*SETP_DEVIATION_LIMIT
1
180
X
X
FLOAT
4
S
*TIME_OUT_MONITOR_VALUE
1
181
X
X
UNSIGNED16 2
D
*TIME_OUT_MONITOR_LIMIT
1
182
X
X
UNSIGNED16 2
S
View
1
200
X
OSTRING
13
D
SETP_DEVIATION_LIMIT
0: Funktion ausgeschaltet,
sonst Grenzwert (7) des Sollwertes. Bei Überschreitung wird 0x02 im 1. Byte der Diagnosisextension
ausgegeben und eine Diagnosemeldung erzeugt.
TIME_OUT_MONITOR
Eine Zeit (100 ms Basis) wird gestartet, wenn der Sollwert das Totband verlässt. Überschreitet diese Zeit
das Limit, wird 0x01 im 1. Byte der Diagnosisextension ausgegeben und eine Diagnosemeldung erzeugt.
Das Bit bleibt 10 s stehen.